Voltage Drop Calculator
Calculate voltage drop for copper and aluminum wire based on wire size, length, and load current. Uses NEC resistance tables for accurate results.
Results
⚠️ Results are for informational purposes only. Verify against applicable codes and manufacturer specifications before use.
How to Calculate Voltage Drop
What Is Voltage Drop?
Voltage drop is the reduction in voltage that occurs as electrical current flows through a wire due to the wire's inherent resistance. Every conductor — whether copper or aluminum — opposes the flow of current, and this opposition converts some electrical energy into heat. The longer the wire run and the higher the current, the greater the voltage drop.
Excessive voltage drop causes motors to overheat, lights to dim, and equipment to malfunction. The National Electrical Code (NEC) recommends keeping voltage drop within acceptable limits to ensure safe and efficient operation.
The Voltage Drop Formula
Single-phase: VD = (2 × L × R × I) / 1000
Three-phase: VD = (√3 × L × R × I) / 1000
VD%: (VD / Voltage) × 100
Where L = one-way distance (ft), R = resistance per 1000 ft (Ω/kft) from NEC Chapter 9 Table 8, I = load current (A)
The NEC recommends a maximum of 3% voltage drop for branch circuits and 5% total (feeder + branch circuit) per NEC 210.19 and 215.2. While these are fine print notes (FPN), most jurisdictions treat them as mandatory.
Worked Example
Scenario: A 20A, 240V single-phase load is located 150 ft from the panel. The wire is 12 AWG copper.
- Resistance of 12 AWG copper = 1.98 Ω/1000 ft (NEC Table 8)
- VD = (2 × 150 × 1.98 × 20) / 1000 = 11.88V
- VD% = (11.88 / 240) × 100 = 4.95%
- This exceeds the 3% limit — upsize to 10 AWG (R = 1.24):
- VD = (2 × 150 × 1.24 × 20) / 1000 = 7.44V → 3.10% (still over!)
- Upsize to 8 AWG (R = 0.778): VD = 4.67V → 1.95% ✓
Practical Tips
- Always calculate voltage drop before pulling wire — upsizing after the fact is expensive.
- Aluminum wire has ~64% more resistance than copper for the same size. Upsize 1–2 AWG sizes when using aluminum.
- For three-phase systems, the √3 multiplier (1.732) is smaller than the single-phase multiplier of 2, so three-phase runs typically have less voltage drop.
- Long runs to outbuildings, well pumps, or remote equipment are the most common source of excessive voltage drop.
Code References
NEC 210.19, NEC 215.2