Wire Size Calculator
Determine the minimum wire size (AWG) for your electrical circuit based on load current, distance, and voltage drop requirements per NEC standards.
Results
⚠️ Results are for informational purposes only. Verify against applicable codes and manufacturer specifications before use.
How to Determine Wire Size
Understanding Wire Sizing (AWG)
Wire size in North America is measured in American Wire Gauge (AWG). Counterintuitively, a smaller AWG number means a larger wire. For example, 10 AWG is larger than 12 AWG and can carry more current. Above 1 AWG, sizes continue as 1/0 (one-ought), 2/0, 3/0, and 4/0, then into kcmil (thousands of circular mils).
Properly sizing wire requires checking two things: (1) the wire's ampacity must handle the load, and (2) the voltage drop over the distance must stay within NEC limits.
NEC Table 310.16 — Ampacity Reference
Wire size is determined by the larger of:
- Ampacity requirement: Wire ampacity ≥ load current (NEC Table 310.16, 75°C column)
- Voltage drop requirement: Voltage drop ≤ 3% for branch circuits, ≤ 5% total
NEC Table 310.16 lists allowable ampacities for copper and aluminum conductors at 60°C, 75°C, and 90°C temperature ratings. For most modern installations, the 75°C column is used because most equipment terminals are rated for 75°C per NEC 110.14(C).
Worked Example
Scenario: Size wire for a 30A, 240V single-phase load, 150 ft run, copper, max 3% voltage drop.
- Ampacity check: 30A load → 10 AWG copper (35A at 75°C) ✓
- Voltage drop check (10 AWG, R = 1.24):
VD = (2 × 150 × 1.24 × 30) / 1000 = 11.16V → 4.65% ✗ (exceeds 3%) - Try 8 AWG (R = 0.778):
VD = (2 × 150 × 0.778 × 30) / 1000 = 7.00V → 2.92% ✓ - Result: Use 8 AWG copper (satisfies both ampacity and voltage drop).
Practical Tips
- Always use the 75°C column for termination ratings unless the equipment is specifically marked for a higher temperature.
- Derate for ambient temperatures above 30°C and for more than 3 current-carrying conductors in a conduit (see NEC 310.15).
- The small conductor rule (NEC 240.4(D)) limits breaker sizes: 14 AWG → 15A, 12 AWG → 20A, 10 AWG → 30A, regardless of ampacity.
- When in doubt, go one size larger — the material cost difference is minimal compared to the safety benefit.
Code References
NEC 310.16, NEC 210.19, NEC 215.2